Introduction to flexible cables (dragging cables)

MICC Cable, short for Mineral Insulated Copper Cable, is commonly referred to as mineral insulated cable or fire-resistant cable in the industry. It is also often known as MI cable.
It is a special type of cable composed of copper conductors, magnesium oxide powder insulation, and a copper sheath. As all its materials are inorganic, it offers exceptional fire resistance and is truly a "non-combustible" cable.
Structure and characteristics of MICC cable(Mineral Insulated Copper Cable)
| The structure of MIC cable from inside to outside: |
| Layer | Material | Function |
| Conductor | Stranded annealed copper wire (Class 1 or Class 2) | Good flexibility, excellent electrical conductivity |
| Insulation | Synthetic mica tape / ceramic silicone rubber tape | High temperature resistance (1375ā„ non-combustible), maintains insulation under flame |
| Filling | Glass fiber rope (optional) | Compact filling, fire and thermal insulation |
| Metal Sheath | Copper tape longitudinally welded and corrugated | Waterproof, mechanical protection, doubles as grounding conductor |
| Outer Sheath | Low smoke halogen free polyolefin (YTTWY model) | Corrosion protection, low smoke, non-toxic |
Core advantages of MICC cable(Mineral Insulated Copper Cable)
Technical Specifications
| Parameter | Specification |
| Rated Voltage | 0.6/1kV |
| Conductor Material | Copper (Class 1 or Class 2 annealed copper) |
| Number of Cores | 1 core, 2 cores, 3 cores, 4 cores, 5 cores, 3+1 core, 3+2 cores, 4+1 core |
| Cross-Sectional Range | Single core: 10–630 mm² |
| Multi-core: 4–150 mm² | |
| Conductor Operating Temperature | Normal: 90°C |
| Overload: 250°C | |
| Installation Temperature | Not below 0°C (preheating required if below 0°C) |
| Minimum Bending Radius | OD ≤ 12mm: 6D |
| OD 12–20mm: 10D | |
| OD 20–40mm: 15D | |
| OD > 40mm: 20D |
Fire Resistance Performance
MICC cable meets stringent international fire resistance test standards:
| Test Item | Standard | Requirement |
| Fire Resistance (C Rating) | BS 6387 | Power supply maintained for 180 minutes under 950℃ flame |
| Fire + Water Spray (W Rating) | BS 6387 | Power supply maintained for 15 minutes under 650℃ flame with water spray |
| Fire + Mechanical Impact (Z Rating) | BS 6387 | Power supply maintained for 15 minutes under 950℃ flame with mechanical impact |
Key Advantages
| Advantage | Description |
| Superior Fire Resistance | Meets BS 6387 C, W, and Z ratings; maintains power supply for over 3 hours under 950℃ flame |
| Long Continuous Length | Single length can exceed 1000 meters with no intermediate joints, reducing failure points |
| Truly Flexible | Corrugated copper sheath design allows coiling for transport; bending radius only 6â€"20 times outer diameter |
| Environmentally Friendly | Inorganic insulation materials produce no halogens, smoke, or toxins when burned; no secondary pollution |
| High Overload Capacity | Normal operating temperature 90آ°C; up to 250آ°C under overload conditions |
| Electromagnetic Shielding | Copper sheath provides complete shielding; no interference with signal cables |
| Corrosion Resistant | Copper sheath offers excellent corrosion resistance; no additional conduit required |
| Long Service Life | Inorganic materials do not age; service life can exceed 100 years under normal operating conditions |
Application Scenarios
| MICC cable is suitable for locations with extremely high fire safety requirements: |
| High-Rise Buildings: Fire elevators, fire pumps, emergency lighting, fire alarm systems |
| Public Transportation: Subways, stations, airports, tunnels |
| Critical Facilities: Hospitals, large shopping malls, exhibition centers, banks, telecommunications buildings |
| Industrial Sites: Steel mills, smelters, petrochemical plants, nuclear power stations |
| National Projects: Major infrastructure projects such as China's FAST (Five-hundred-meter Aperture Spherical Telescope) |
Comparison with Other Fire-Resistant Cables
| Model | Insulation Material | Metal Sheath | Characteristics | Application Scenarios |
| YTTW | Mica Tape | Corrugated Copper Tube | Good flexibility, long continuous length, moderate cost | Fire protection main lines in high-rise buildings |
| BTTW | Magnesium Oxide | Seamless Copper Tube | Rigid, optimal fire resistance, recoverable after breakdown | Nuclear power stations, super high-rise core fire protection |
| BTLY | Mica Tape | Aluminum Tube + Isolation Layer | Lower cost, good water and explosion resistance | General fire protection applications |
| BBTRZ | Ceramic Silicone Rubber | Non-metallic Sheath | Non-metallic sheath, maximum flexibility | Space-constrained installations |
Common specifications of MICC cables
1. Number of Cores and Cross-Section Range
| Core Type | Cross-Section Range (mm虏) | Description |
| 1 Core | 10 ~ 630 | Single-phase high current main line |
| 2 Cores | 4 ~ 150 | Single-phase power supply |
| 3 Cores | 4 ~ 150 | Three-phase three-wire |
| 4 Cores | 4 ~ 150 | Three-phase four-wire |
| 5 Cores | 4 ~ 150 | Three-phase five-wire (with ground) |
| 3+1 Core | 4 ~ 150 | Three-phase + neutral |
| 3+2 Cores | 4 ~ 150 | Three-phase + neutral + ground |
| 4+1 Core | 4 ~ 150 | Three-phase four-wire + ground |
2. 1-Core YTTW Cable Specifications
| Nominal Cross-Section (mm²) | Insulation Thickness (mm) | Copper Sheath Thickness (mm) | Approx. Outer Diameter (mm) | Current Carrying Capacity in Air (A) | Voltage Drop (V/A.km) |
| 1×10 | 1 | 0.5 | 7.02 | 97 | 2.33 |
| 1×16 | 1 | 0.6 | 8.24 | 125 | 1.47 |
| 1×25 | 1 | 0.6 | 9.56 | 165 | 0.92 |
| 1×35 | 1 | 0.6 | 10.7 | 200 | 0.67 |
| 1×50 | 1.2 | 0.7 | 12.6 | 245 | 0.49 |
| 1×70 | 1.2 | 0.7 | 14.4 | 305 | 0.34 |
| 1×95 | 1.2 | 0.8 | 16.5 | 375 | 0.25 |
| 1×120 | 1.2 | 0.8 | 18.14 | 435 | 0.2 |
| 1×150 | 1.4 | 0.8 | 20.15 | 500 | 0.16 |
| 1×185 | 1.4 | 0.9 | 22.1 | 580 | 0.13 |
| 1×240 | 1.4 | 0.9 | 24.85 | 685 | 0.1 |
| 1×300 | 1.6 | 1 | 27.7 | 795 | 0.08 |
| 1×400 | 1.6 | 1 | 30.4 | 930 | 0.06 |
3. 2-Core YTTW Cable Specifications
| Nominal Cross-Section (mm²) | Insulation Thickness (mm) | Copper Sheath Thickness (mm) | Approx. Outer Diameter (mm) | Current Carrying Capacity in Air (A) | Voltage Drop (V/A.km) |
| 2×2.5 | 0.8 | 0.5 | 6.96 | 33 | 18.96 |
| 2×4.0 | 0.8 | 0.6 | 8.1 | 44 | 11.8 |
| 2×6.0 | 0.8 | 0.6 | 9.12 | 57 | 7.8 |
| 2×10 | 1 | 0.7 | 12.44 | 78 | 4.66 |
| 2×16 | 1 | 0.7 | 14.48 | 104 | 2.86 |
| 2×25 | 1 | 0.8 | 17.32 | 135 | 2.52 |
| 2×35 | 1.1 | 0.8 | 19.9 | 168 | 2.24 |
| 2×50 | 1.2 | 0.9 | 23 | 204 | 1.64 |
| 2×70 | 1.2 | 1 | 26.8 | 263 | 1.42 |
| 2×95 | 1.2 | 1 | 30.6 | 320 | 1.08 |
| 2×120 | 1.2 | 1 | 33.88 | 373 | 0.98 |
| 2×150 | 1.4 | 1 | 37.7 | 430 | 0.88 |
| 2×185 | 1.4 | 1 | 41.2 | 493 | 0.72 |
4. 3-Core YTTW Cable Specifications
| Nominal Cross-Section (mm²) | Insulation Thickness (mm) | Copper Sheath Thickness (mm) | Approx. Outer Diameter (mm) | Current Carrying Capacity in Air (A) | Voltage Drop (V/A.km) |
| 3×2.5 | 0.8 | 0.6 | 7.56 | 29 | 16.4 |
| 3×4.0 | 0.8 | 0.6 | 8.57 | 38 | 10.2 |
| 3×6.0 | 0.8 | 0.6 | 9.67 | 46 | 6.74 |
| 3×10 | 1 | 0.7 | 13.22 | 65 | 4.03 |
| 3×16 | 1 | 0.7 | 15.42 | 85 | 2.54 |
| 3×25 | 1 | 0.8 | 18.46 | 118 | 1.59 |
| 3×35 | 1.1 | 0.8 | 21.43 | 150 | 1.16 |
| 3×50 | 1.2 | 0.9 | 24.55 | 192 | 0.85 |
| 3×70 | 1.2 | 1 | 28.63 | 228 | 0.59 |
| 3×95 | 1.2 | 1 | 32.72 | 273 | 0.43 |
| 3×120 | 1.2 | 1 | 36.26 | 314 | 0.35 |
| 3×150 | 1.4 | 1 | 40.56 | 360 | 0.28 |
| 3×185 | 1.4 | 1 | 44.33 | 410 | 0.22 |
5. 4-Core YTTW Cable Specifications
| Nominal Cross-Section (mm²) | Insulation Thickness (mm) | Copper Sheath Thickness (mm) | Approx. Outer Diameter (mm) | Current Carrying Capacity in Air (A) | Voltage Drop (V/A.km) |
| 4×6.0 | 0.8 | 0.6 | 10.59 | 46 | 6.74 |
| 4×10 | 1 | 0.7 | 14.52 | 65 | 4.03 |
| 4×16 | 1 | 0.8 | 17.18 | 85 | 2.54 |
| 4×25 | 1 | 0.9 | 20.57 | 118 | 1.59 |
| 4×35 | 1.1 | 1 | 23.86 | 150 | 1.16 |
| 4×50 | 1.2 | 1 | 27.34 | 192 | 0.85 |
| 4×70 | 1.2 | 1 | 31.69 | 228 | 0.59 |
| 4×95 | 1.2 | 1 | 36.27 | 273 | 0.43 |
| 4×120 | 1.2 | 1.1 | 40.43 | 314 | 0.35 |
| 4×150 | 1.4 | 1.1 | 45 | 360 | 0.28 |
| 4×185 | 1.4 | 1.2 | 49.42 | 410 | 0.22 |
certificate
Our Certificate

CE

TUV

SAA

U.L
packing and shipping
packaging and shipping

export packaging
Moisture prevention: A desiccant (silica gel packet) must be placed inside the coiled cable, and the humidity indicator card should be checked before sealing the film.
Fumigation: If wooden pallets or trays are used for export, they must bear the IPPC (International Plant Protection Convention) fumigation mark, otherwise they may be destroyed or subject to mandatory treatment at the destination port.
Label: The shipping mark must be firmly affixed, including the contract number, gross weight, reel number, as well as marks such as "Do Not Stack" and "Keep Dry".
Multiple modes of transportation
Providing one-stop logistics services such as "door-to-port" or "door-to-door" can simplify the communication process and offer more cost-effective integrated freight rates.

JSH Cable Advantages
Advanced equipment
Advanced equipment and multiple production lines are the guarantee of our cable quality and production capacity.




Application: Our cables have been extensively used in municipal, electric power, water conservancy, steel, coal, petroleum, chemical, construction, subway, high-speed rail, airport, and other fields.
Advanced Equipment and Reliable Technology: We employ cutting-edge equipment and reliable technology to ensure the manufacturing of superior products.
Ustomer Satisfaction: Our excellent management practices, along with guaranteed quality and reliable technical support, provide customers with reliable products and satisfactory services.
Extensive Market Reach: Our products have been distributed across more than 30 provinces and regions in China and exported to over 20 countries, including Russia, Spain, and the United States.
FAQ
Q1: Are you a factory or trading company?
A1: We are a manufacturer.
Q2: Can I send you here to purchase samples of MICC cable(Mineral Insulated Copper Cable)?
A2: Yes! You are welcome to place sample order to test our superior quality and services.
Q3: What is your Warranty?
A3: All the products will have 12 months Warranty.
Q4:What payment method do you accept?
A4:T/T(Bank transfer), L/C, Western Union, Money Gram, Paypal, etc.
Q5: Can you put my brand name (logo) on these products?
A5: Yes! The professional OEM services will be welcomed to us. Our factory accepts to make the logo free for
bulk orders.
Q6: May I know the status of my order?
A6: Yes .The order information and photos at different production stage of your order will be sent to you and the information will be updated in time.
Q7: What's the leading time? (How long do you need to prepare my goods? )
A7: Delivery (no more than 1000pcs) will be arranged within 3-7 days after payment, and arrive you within about 3-7 working days via international express.
contact us
![]()
tel: +86-13891913198
![]()
Email: Penn@sxjshsm.com
![]()
Whatsapp: +86-13891913198
![]()
Wechat: 13891913198
Hot Tags: micc cable(mineral insulated copper cable), China micc cable(mineral insulated copper cable) manufacturers, suppliers, factory, fire alarm power cable, tvvb elevator cable, special cable company, es h09z h battery cable, elevator power cable, 16 2 fire alarm cable