MICC Cable(Mineral Insulated Copper Cable)

Rated Voltage: 0.6/1kV
Conductor Material: Copper (Class 1 or Class 2 annealed copper)
Number of Cores: 1 core, 2 cores, 3 cores, 4 cores, 5 cores, 3+1 core, 3+2 cores, 4+1 core
Cross-Sectional Range: Single core: 10–630 mm² Multi-core: 4–150 mm²
Conductor Operating Temperature Normal: 90°C Overload: 250°C
Installation Temperature: Not below 0°C (preheating required if below 0°C)
Minimum Bending Radius:
OD ≤ 12mm: 6D OD 12–20mm: 10D OD 20–40mm: 15D OD > 40mm: 20D
Manufacturer: JSH Cable
Send Inquiry
Description

Introduction to flexible cables (dragging cables)

 

MICC cable(Mineral Insulated Copper Cable)

MICC Cable, short for Mineral Insulated Copper Cable, is commonly referred to as mineral insulated cable or fire-resistant cable in the industry. It is also often known as MI cable.

It is a special type of cable composed of copper conductors, magnesium oxide powder insulation, and a copper sheath. As all its materials are inorganic, it offers exceptional fire resistance and is truly a "non-combustible" cable.

Structure and characteristics of  MICC cable(Mineral Insulated Copper Cable)

 

The structure of MIC cable from inside to outside:
Layer Material Function
Conductor Stranded annealed copper wire (Class 1 or Class 2) Good flexibility, excellent electrical conductivity
Insulation Synthetic mica tape / ceramic silicone rubber tape High temperature resistance (1375℃ non-combustible), maintains insulation under flame
Filling Glass fiber rope (optional) Compact filling, fire and thermal insulation
Metal Sheath Copper tape longitudinally welded and corrugated Waterproof, mechanical protection, doubles as grounding conductor
Outer Sheath Low smoke halogen free polyolefin (YTTWY model) Corrosion protection, low smoke, non-toxic

 

 

Core advantages of MICC cable(Mineral Insulated Copper Cable)

Technical Specifications

Parameter Specification
Rated Voltage 0.6/1kV
Conductor Material Copper (Class 1 or Class 2 annealed copper)
Number of Cores 1 core, 2 cores, 3 cores, 4 cores, 5 cores, 3+1 core, 3+2 cores, 4+1 core
Cross-Sectional Range Single core: 10–630 mm²
Multi-core: 4–150 mm²
Conductor Operating Temperature Normal: 90°C
Overload: 250°C
Installation Temperature Not below 0°C (preheating required if below 0°C)
Minimum Bending Radius OD ≤ 12mm: 6D
OD 12–20mm: 10D
OD 20–40mm: 15D
OD > 40mm: 20D

 

Fire Resistance Performance

MICC cable meets stringent international fire resistance test standards:

Test Item Standard Requirement
Fire Resistance (C Rating) BS 6387 Power supply maintained for 180 minutes under 950℃ flame
Fire + Water Spray (W Rating) BS 6387 Power supply maintained for 15 minutes under 650℃ flame with water spray
Fire + Mechanical Impact (Z Rating) BS 6387 Power supply maintained for 15 minutes under 950℃ flame with mechanical impact

 

Key Advantages

Advantage Description
Superior Fire Resistance Meets BS 6387 C, W, and Z ratings; maintains power supply for over 3 hours under 950℃ flame
Long Continuous Length Single length can exceed 1000 meters with no intermediate joints, reducing failure points
Truly Flexible Corrugated copper sheath design allows coiling for transport; bending radius only 6â€"20 times outer diameter
Environmentally Friendly Inorganic insulation materials produce no halogens, smoke, or toxins when burned; no secondary pollution
High Overload Capacity Normal operating temperature 90آ°C; up to 250آ°C under overload conditions
Electromagnetic Shielding Copper sheath provides complete shielding; no interference with signal cables
Corrosion Resistant Copper sheath offers excellent corrosion resistance; no additional conduit required
Long Service Life Inorganic materials do not age; service life can exceed 100 years under normal operating conditions

Application Scenarios

MICC cable is suitable for locations with extremely high fire safety requirements:
High-Rise Buildings: Fire elevators, fire pumps, emergency lighting, fire alarm systems
Public Transportation: Subways, stations, airports, tunnels
Critical Facilities: Hospitals, large shopping malls, exhibition centers, banks, telecommunications buildings
Industrial Sites: Steel mills, smelters, petrochemical plants, nuclear power stations
National Projects: Major infrastructure projects such as China's FAST (Five-hundred-meter Aperture Spherical Telescope)

 

Comparison with Other Fire-Resistant Cables

 

Model Insulation Material Metal Sheath Characteristics Application Scenarios
YTTW Mica Tape Corrugated Copper Tube Good flexibility, long continuous length, moderate cost Fire protection main lines in high-rise buildings
BTTW Magnesium Oxide Seamless Copper Tube Rigid, optimal fire resistance, recoverable after breakdown Nuclear power stations, super high-rise core fire protection
BTLY Mica Tape Aluminum Tube + Isolation Layer Lower cost, good water and explosion resistance General fire protection applications
BBTRZ Ceramic Silicone Rubber Non-metallic Sheath Non-metallic sheath, maximum flexibility Space-constrained installations

 

Common specifications of MICC cables

 

1. Number of Cores and Cross-Section Range

 

Core Type Cross-Section Range (mm虏) Description
1 Core 10 ~ 630 Single-phase high current main line
2 Cores 4 ~ 150 Single-phase power supply
3 Cores 4 ~ 150 Three-phase three-wire
4 Cores 4 ~ 150 Three-phase four-wire
5 Cores 4 ~ 150 Three-phase five-wire (with ground)
3+1 Core 4 ~ 150 Three-phase + neutral
3+2 Cores 4 ~ 150 Three-phase + neutral + ground
4+1 Core 4 ~ 150 Three-phase four-wire + ground

 

2. 1-Core YTTW Cable Specifications

 

Nominal Cross-Section (mm²) Insulation Thickness (mm) Copper Sheath Thickness (mm) Approx. Outer Diameter (mm) Current Carrying Capacity in Air (A) Voltage Drop (V/A.km)
1×10 1 0.5 7.02 97 2.33
1×16 1 0.6 8.24 125 1.47
1×25 1 0.6 9.56 165 0.92
1×35 1 0.6 10.7 200 0.67
1×50 1.2 0.7 12.6 245 0.49
1×70 1.2 0.7 14.4 305 0.34
1×95 1.2 0.8 16.5 375 0.25
1×120 1.2 0.8 18.14 435 0.2
1×150 1.4 0.8 20.15 500 0.16
1×185 1.4 0.9 22.1 580 0.13
1×240 1.4 0.9 24.85 685 0.1
1×300 1.6 1 27.7 795 0.08
1×400 1.6 1 30.4 930 0.06

 

3. 2-Core YTTW Cable Specifications

 

Nominal Cross-Section (mm²) Insulation Thickness (mm) Copper Sheath Thickness (mm) Approx. Outer Diameter (mm) Current Carrying Capacity in Air (A) Voltage Drop (V/A.km)
2×2.5 0.8 0.5 6.96 33 18.96
2×4.0 0.8 0.6 8.1 44 11.8
2×6.0 0.8 0.6 9.12 57 7.8
2×10 1 0.7 12.44 78 4.66
2×16 1 0.7 14.48 104 2.86
2×25 1 0.8 17.32 135 2.52
2×35 1.1 0.8 19.9 168 2.24
2×50 1.2 0.9 23 204 1.64
2×70 1.2 1 26.8 263 1.42
2×95 1.2 1 30.6 320 1.08
2×120 1.2 1 33.88 373 0.98
2×150 1.4 1 37.7 430 0.88
2×185 1.4 1 41.2 493 0.72

 

4. 3-Core YTTW Cable Specifications

 

Nominal Cross-Section (mm²) Insulation Thickness (mm) Copper Sheath Thickness (mm) Approx. Outer Diameter (mm) Current Carrying Capacity in Air (A) Voltage Drop (V/A.km)
3×2.5 0.8 0.6 7.56 29 16.4
3×4.0 0.8 0.6 8.57 38 10.2
3×6.0 0.8 0.6 9.67 46 6.74
3×10 1 0.7 13.22 65 4.03
3×16 1 0.7 15.42 85 2.54
3×25 1 0.8 18.46 118 1.59
3×35 1.1 0.8 21.43 150 1.16
3×50 1.2 0.9 24.55 192 0.85
3×70 1.2 1 28.63 228 0.59
3×95 1.2 1 32.72 273 0.43
3×120 1.2 1 36.26 314 0.35
3×150 1.4 1 40.56 360 0.28
3×185 1.4 1 44.33 410 0.22

 

5. 4-Core YTTW Cable Specifications

 

Nominal Cross-Section (mm²) Insulation Thickness (mm) Copper Sheath Thickness (mm) Approx. Outer Diameter (mm) Current Carrying Capacity in Air (A) Voltage Drop (V/A.km)
4×6.0 0.8 0.6 10.59 46 6.74
4×10 1 0.7 14.52 65 4.03
4×16 1 0.8 17.18 85 2.54
4×25 1 0.9 20.57 118 1.59
4×35 1.1 1 23.86 150 1.16
4×50 1.2 1 27.34 192 0.85
4×70 1.2 1 31.69 228 0.59
4×95 1.2 1 36.27 273 0.43
4×120 1.2 1.1 40.43 314 0.35
4×150 1.4 1.1 45 360 0.28
4×185 1.4 1.2 49.42 410 0.22

 

certificate

 

 

Our Certificate

CE

 

CE

TUV

TUV

SAA

SAA

UL

U.L

packing and shipping

 

 
 
packaging and shipping
ABC Cable (Aerial Bundled Cable)
01.

export packaging

Moisture prevention: A desiccant (silica gel packet) must be placed inside the coiled cable, and the humidity indicator card should be checked before sealing the film.
Fumigation: If wooden pallets or trays are used for export, they must bear the IPPC (International Plant Protection Convention) fumigation mark, otherwise they may be destroyed or subject to mandatory treatment at the destination port.
Label: The shipping mark must be firmly affixed, including the contract number, gross weight, reel number, as well as marks such as "Do Not Stack" and "Keep Dry".

02.

Multiple modes of transportation

Providing one-stop logistics services such as "door-to-port" or "door-to-door" can simplify the communication process and offer more cost-effective integrated freight rates.

ABC Cable (Aerial Bundled Cable)

JSH Cable Advantages

 

Advanced equipment

Advanced equipment and multiple production lines are the guarantee of our cable quality and production capacity.

ABC Cable (Aerial Bundled Cable)
ABC Cable (Aerial Bundled Cable)
ABC Cable (Aerial Bundled Cable)
ABC Cable (Aerial Bundled Cable)

Application: Our cables have been extensively used in municipal, electric power, water conservancy, steel, coal, petroleum, chemical, construction, subway, high-speed rail, airport, and other fields.

 

Advanced Equipment and Reliable Technology: We employ cutting-edge equipment and reliable technology to ensure the manufacturing of superior products.

 

Ustomer Satisfaction: Our excellent management practices, along with guaranteed quality and reliable technical support, provide customers with reliable products and satisfactory services.

 

Extensive Market Reach: Our products have been distributed across more than 30 provinces and regions in China and exported to over 20 countries, including Russia, Spain, and the United States.

 

FAQ

 

Q1: Are you a factory or trading company?

A1: We are a manufacturer.

Q2: Can I send you here to purchase samples of MICC cable(Mineral Insulated Copper Cable)?
A2: Yes! You are welcome to place sample order to test our superior quality and services.

Q3: What is your Warranty?
A3: All the products will have 12 months Warranty.

Q4:What payment method do you accept?
A4:T/T(Bank transfer), L/C, Western Union, Money Gram, Paypal, etc.

Q5: Can you put my brand name (logo) on these products?
A5: Yes! The professional OEM services will be welcomed to us. Our factory accepts to make the logo free for
bulk orders.

Q6: May I know the status of my order?
A6: Yes .The order information and photos at different production stage of your order will be sent to you and the information will be updated in time.

Q7: What's the leading time? (How long do you need to prepare my goods? )
A7: Delivery (no more than 1000pcs) will be arranged within 3-7 days after payment, and arrive you within about 3-7 working days via international express.

contact us

 

 

tel.png

tel: +86-13891913198

envelope.png

Email: Penn@sxjshsm.com

address.png

Whatsapp: +86-13891913198

fax.png

Wechat: 13891913198

 

Hot Tags: micc cable(mineral insulated copper cable), China micc cable(mineral insulated copper cable) manufacturers, suppliers, factory, fire alarm power cable, tvvb elevator cable, special cable company, es h09z h battery cable, elevator power cable, 16 2 fire alarm cable